Adjustable Moulded Case Circuit Breaker

Adjustable Moulded Case Circuit Breaker

Unit Price
250 Frame is $57.00~$93.50/Unit
630 Frame is $122.00~$192.5/Unit
1600 Frame is $355.00~$560.00/Unit
Send Inquiry
Company Information

company information

 

Test Report and Certificate

Test Report and Certificate

 

Application

 

SRIZOU adjustable moulded case circuit breaker with insulation voltage up to 800V, this product is applicable for distribution systerm of AC 50/ 60Hz, rated working voltage 690V and rated working current from 16A to 1600A. The adjustable moulded case circuit breaker will provide protection for the circuit and equipment in case of overload, short circuit and under voltage condition occurred in the power distribution circuit. Besides, it can also provide protection of overload, short circuit and under voltage for the non-frequent start of motor.

It is in conformity of IEC60947-2 standards.

 

Product Details

 

6

 

Product Parameters

 

Part 1 - ADM3E-250S/H

Frame Size

ADM3E-250

Rated Working Voltage

Ue=AC380/400/415V, AC550V,AC690V

No. Of Poles

3P

Rated Insulation Voltage

800V AC50/60Hz

Type of Release

Electronic

In

40A

100A

160A

250A

Long-time-delay protection

Current Ir(A)

16, 18, 20, 23, 25, 28, 32, 32, 36, 40

Ir=(0.4-1)In

40, 45, 50, 55, 63, 70, 80, 90, 100

Ir=(0.4-1)In

63, 70, 80, 90, 100, 110, 125, 150, 160

Ir=(0.4-1)In

100, 110, 125, 140, 160, 175, 200, 225, 250

Ir=(0.4-1)In

Time Setting

64S

Short-time-delay protection

current Isd(A)

Isd=(5-13)Ir

Isd=(5-13)Ir

Isd=(5-13)Ir

Isd=(5-13)Ir

Time Setting

0.3S

Instantaneous action protection

current Ii(A)

Ii=15In

Ii=15In

Ii=15In

Ii=12In

Trip Time

≤60ms

Icu/Ics

S

H

Ics= Icu=70kA at AC380/400/415V

Ics= Icu=40kA at 550V

Ics= Icu=15kA at 690V

Ics=Icu=100kA at AC380/400/415V

Ics= Icu=50kA at 550V

Ics= Icu=25kA at 690V

Dimension(MM)

105x161X86MM

 

Part 2 - ADM3E-630S/H

Frame Size

ADM3E-630

Rated Working Voltage

Ue=AC380/400/415V, AC550V,AC690V

No. Of Poles

3P

Rated Insulation Voltage

800V AC50/60Hz

Type of Release

Electronic

In

400A

630A

Long-time-delay protection

Current Ir(A)

160, 180, 200, 230, 250, 280, 320, 350, 400

Ir=(0.4-1)In

250, 280, 320, 350, 400, 400, 450, 500, 570, 630

Ir=(0.4-1)In

Time Setting

64S

Short-time-delay protection

 

current Isd(A)

Isd=(5-13)Ir

Isd=(5-13)Ir

Time Setting

0.3S

Instantaneous action protection

current Ii(A)

Ii=12In

Ii=11In

Trip Time

≤60ms

Icu/Ics

S

H

Ics= Icu=70kA at AC380/400/415V

Ics= Icu=40kA at 550V

Ics= Icu=15kA at 690V

Ics=Icu=100kA at AC380/400/415V

Ics= Icu=50kA at 550V

Ics= Icu=25kA at 690V

Dimension(MM)

140x255x110MM

 

Part 3 - ADM3E-1600S/H

Frame Size

ADM3E-1600

Rated Working Voltage

Ue=AC380/400/415V, AC550V,AC690V

No. Of Poles

3P

Rated Insulation Voltage

800V AC50/60Hz

Type of Release

Electronic

In

800A

1000A

1250A

1600A

Long-time-delay protection

Current Ir(A)

Ir=320-800

Ir=(0.4-1)In

Ir=400-1000

Ir=(0.4-1)In

Ir=500-1250A

Ir=(0.4-1)In

Ir=640-1600A

Ir=(0.4-1)In

Time Setting(S)

Tr: 0.5, 1, 2, 4, 8, 12, 16, 20, 24, OFF, at 6Ir

Short-time-delay protection

 

current Isd(A)

Isd= (1.5-10)Ir

Isd= (1.5-10)Ir

Isd= (1.5-10)Ir

Isd= (1.5-10)Ir

Time Setting

Tsd: 0.1,0.2,0.3,0.4 OFF

Instantaneous action protection

current Ii(A)

Ii=(2-15)In

Ii=(2-15)In

Ii=(2-15)In

Ii=(2-15)In

Trip Time

≤60ms

Icu/Ics

S

H

Ics= Icu=50kA at AC380/400/415V

Ics= Icu=20kA at 550V

Ics= Icu=15kA at 690V

Ics=Icu=70kA at AC380/400/415V

Ics= Icu=30kA at 550V

Ics= Icu=25kA at 690V

Dimension(MM)

327x210x147MM

Remarks:
S - Standard Type
H - High Breaking Ability Type

 

Packing & Shipping

 

1

 

FAQ

 

FAQ

 

Hot Tags: adjustable moulded case circuit breaker, China adjustable moulded case circuit breaker manufacturers, suppliers, factory

Next:No Information

Send Inquiry